Chiller not cooling enough: a checklist with numbers
Chiller not cooling enough: a checklist with numbers

Chiller not cooling enough: a checklist with numbers

A chiller that has lost part of its capacity often shows no alarm at all. The leaving water temperature simply drifts above the setpoint, first on warm afternoons and then all day. The table below is the checklist we work through. Each line has a reading that confirms or excludes the cause, so the search does not depend on guesswork.

The checklist

CauseReading that points to itRepair
Dirty condenser coilCondensing temperature far above outdoor air temperatureCoil cleaning from the inside out
Refrigerant shortageLow suction pressure, high superheat, low subcoolingLeak search, repair, recharge by weight
Low water flowLarge temperature difference across the evaporatorStrainer, pump, balancing valves
Fouled evaporatorGrowing gap between evaporating and leaving water temperatureChemical cleaning of the water side
Wrong glycol concentrationRefractometer reading above the design valueCorrect the mixture
Capacity control faultCurrent shows that a compressor or stage is not loadingRepair valve, slide or controller output
Load has grownMeasured capacity equals the data sheet, yet it is not enoughBuffer tank, second unit, rental

Air side: the condenser

Underside of a chiller condenser coil with dirt between the fins

On an air cooled chiller the coil is the first thing to look at, also from underneath and from the inside, where dirt is hidden from view. A blocked coil raises the condensing pressure, cuts capacity and increases power draw at the same time. Our note on what a dirty condenser costs gives a worked example, and the service is described under condenser cleaning.

Refrigerant side: charge and expansion

We read suction and discharge pressure, superheat and subcooling on every circuit and compare the circuits with each other. A circuit that is short of refrigerant uses only part of its evaporator. An expansion valve that does not open far enough produces a similar picture with normal subcooling. The difference matters, because one needs a leak repair and the other a valve or driver. See refrigerant leak repair.

Water side: flow, fouling and glycol

Refractometer scale used to read glycol concentration

Flow is checked from the pressure drop across the evaporator and the temperature difference between inlet and outlet. Too little flow makes the controller reduce capacity to protect the evaporator from freezing. Deposits on the water side act as insulation. Glycol deserves its own measurement: every extra ten percent lowers heat transfer and raises the pressure drop, so a mixture that is stronger than the design value quietly takes capacity away. We adjust it after a glycol test.

Controls: is the whole machine working?

A compressor locked out by an old alarm, an unloader stuck open or a demand limit left active after commissioning can hold the unit at part load for months. The controller display looks calm. Current per compressor and the stage status tell the truth. We step through the stages one by one and compare them with the manufacturer data.

When the chiller is simply too small

If measured capacity matches the data sheet, the chiller is healthy and the process has outgrown it. A capacity measurement from flow and temperature difference settles this within an hour. The options then are a buffer tank for short peaks, a second chiller or a rental unit for the season.

What a diagnosis costs

On site diagnosis starts at 800 EUR net, a working hour is 115 EUR net and travel 0.75 EUR net per km. You receive the readings, the calculated capacity and a list of actions in order of effect. Our crews travel from Wałsnów and Szczecin in Poland. Regular checks following the maintenance checklist prevent most of the causes above.

Quick answers

Why is there no alarm when the chiller cannot hold the setpoint?
Alarms watch limits. A slow loss of capacity stays inside those limits and only shows when the load is high.
Will a lower setpoint help?
No. The unit is already giving all the capacity it has, and a lower setpoint only raises the risk of freezing the evaporator.
What can I check myself?
The strainer, the state of the coil, the water temperature difference and whether all compressors are running.
How long does the diagnosis take?
Usually a few hours, provided the chiller can run under load while we measure.