DiagnosticsSzczecin, PolandMon to Sat8:00 to 16:00 CETService baseWałsnów 22b, Poland
info@chillerserwis.com
Chiller maintenance checklist: 24 points and the report
Chiller maintenance checklist: 24 points and the report

Chiller maintenance checklist: 24 points and the report

A chiller maintenance visit is worth paying for when it follows a written checklist and ends with a report you can compare with last year. Too many operators receive an invoice, a signature and the words “all fine”, and three months later the unit trips on high pressure. Below is the 24 point checklist we work through on every chiller maintenance, the readings that go into the report, what a maintenance contract covers and what you can check yourself between visits.

Air-cooled MTA chiller with panels removed during a maintenance visit

Why a checklist beats a visual inspection

A chiller has three systems that affect each other: the refrigerant circuit, the chilled water circuit and the electrical and control side. A visual inspection catches what is visible from outside, such as a dirty coil, oil stains or loose panels. The expensive failures start where you have to measure. A compressor running at 15 K superheat looks normal for weeks while it loses oil. A flow switch that still does not trip at 70 percent of design flow no longer protects the evaporator. That is why our maintenance consists of measured points with target values, not of a walk around the unit.

The 24 point chiller maintenance checklist

The list applies to air-cooled and water-cooled chillers with scroll or screw compressors. On dual circuit units every circuit is recorded separately.

AreaCheckTarget value or criterion
RefrigerantSuperheat at evaporator outlet5 to 8 K scroll, 6 to 10 K screw
RefrigerantSubcooling at condenser outlet3 to 8 K, higher suggests overcharge
RefrigerantCondensing temperature versus ambient12 to 18 K above ambient with a clean coil
RefrigerantSight glass and moisture indicatorno bubbles, indicator green
RefrigerantCompressor oil level and coloursight glass 1/4 to 3/4, oil clear
RefrigerantLeak check under F-gas Regulation (EU) 2024/573every 12, 6 or 3 months depending on CO2 equivalent
Chilled waterSupply to return temperature difference4 to 6 K at design load
Chilled waterPressure drop across evaporator and strainerstrainer below 0.3 bar, otherwise clean
Chilled waterGlycol concentration and pHfreeze point 5 K below lowest temperature, pH 7.5 to 9
Chilled waterFlow switch trip pointtrips at 60 to 70 % of design flow
ElectricalCompressor current per phasephase imbalance below 5 %
ElectricalContactors, terminals, insulation resistanceterminals torqued, insulation above 1 MΩ
ControlsAlarm log, start frequencyunder 6 starts per hour per compressor

The remaining points cover condenser fans (bearing noise, speed controller), the expansion valve (stroke, bulb fixing), the crankcase heater, evaporator insulation, the chilled water pump, the expansion vessel and the safety valves. Every point gets a reading or a dated “OK” in the report.

Pressure gauges on the chiller panel read during maintenance

Readings we record in every report

The maintenance report is the basis for the next decision: repair, upgrade or replacement. We record the same values every time so that you can see trends. If condensing temperature rises year after year at the same ambient, the coil fouls faster than it is cleaned. If subcooling drops, the circuit is losing refrigerant even before the leak check finds the spot. If compressor current rises at the same load, the mechanics are wearing.

Every report contains: ambient temperature and time of measurement, chilled water supply and return, suction and discharge pressure per circuit, superheat and subcooling, current per phase, glycol concentration, strainer pressure drop, alarm log of the last 30 days, running hours and start counter, plus photos of the nameplate, the coil and the control panel.

Maintenance before winter and before summer

A chiller that runs all year needs two different visits. Before summer the focus is the condenser and the fans, because the unit reaches its limit at 35 °C ambient. Before winter we check antifreeze, the crankcase heater, fan speed control for low condensing pressure and trace heating on the pipework. What goes wrong in winter operation is covered in how to prepare a chiller for winter. For units that run only in season, one visit before start-up plus a mid-season coil check is enough.

Compressor and refrigerant piping checked for oil traces during chiller maintenance

What a maintenance contract includes, and what it does not

Our maintenance contracts have fixed dates, a fixed checklist and a fixed report. The contract covers the visits, the F-gas leak check, the logbook entry and the documentation of all readings. Spare parts and refrigerant are charged as used. The contract does not include a standby fee or an emergency service with response time. We sell working hours with a report, not availability. Faults between visits are handled as a repair order with its own quote, as described on the chilled water unit repair page.

For sites outside Poland we charge travel at 0.75 EUR per kilometre and labour at 115 EUR per hour. A first diagnosis with a full measurement report starts at 800 EUR net. The report is yours and can be handed to any other contractor.

What your maintenance team can check between visits

  • Once a month look at the condenser coil for leaves, seed fluff and dust, and rinse it with a soft water jet from inside out.
  • Once a week write down supply and return temperature and system pressure.
  • After every alarm note the code, the time and the outdoor temperature instead of just resetting it.
  • Clean the chilled water strainer once a quarter if the pressure drop exceeds 0.3 bar.
  • Report oil traces under the compressor or at brazed joints at once, do not wipe them off.

The meaning of each code is in our list of chiller alarm codes, and the legal leak check interval comes out of the chiller inspection calculator.

Frequently asked questions about chiller maintenance

How often should a chiller be serviced?
Twice a year for units in year-round operation, once before summer and once before winter. Seasonal units need one visit before start-up. The F-gas leak check has its own intervals that depend on the charge in CO2 equivalent.
How long does a maintenance visit take?
About 3 to 4 hours for an air-cooled chiller with one circuit, 5 to 7 hours for dual circuit or screw units. Coil cleaning is added depending on fouling.
Does maintenance replace the leak check?
No. The leak check is a separate item with its own logbook entry. We carry it out during the visit when it is due and document it separately.
What does a maintenance visit cost?
We charge 115 EUR per working hour and 0.75 EUR per kilometre travel. Parts and refrigerant are charged as used. A quote is based on the nameplate, the site and the number of units.
Do I need a maintenance contract?
A contract secures the dates and makes the reports comparable. It is not compulsory. Many operators order a single maintenance visit with a report first and decide afterwards.

Would you like a maintenance visit with a checklist and a report? Send the manufacturer, model, site and the last report if you have one through the contact form or to info@chillerserwis.com. You will receive a quote with the scope and a proposed date.

Request service